HV Tan Delta Tester MCTD001,dissipation factor tester, power factor test set
Product Summary
Features 1. The instrument uses Fourier transform digital filtering technology to measure capacitance, dielectric loss and other parameters. The test result has high precision and is easy to realize automatic measurement. 2. The instrument adopts frequency conversion technology to eliminate 50Hz ...
Product Custom Attributes
Basic Properties
Trading Properties
Product Description
Features
1. The instrument uses Fourier transform digital filtering technology to measure capacitance, dielectric loss and other parameters. The test result has high precision and is easy to realize automatic measurement.
2. The instrument adopts frequency conversion technology to eliminate 50Hz power frequency interference in the field. Even in the environment of strong electromagnetic interference, reliable data can be measured.
3. It is easy to operate with full touch LCD. Full touch LCD screen, super full graphics operation interface, each process is very clear, operators can use without additional professional training. The whole process can be measured by touch.
4. Storage data: It is equipped with a calendar chip and a large-capacity memory, which can save the test results at any time, view the historical records at any time, and print out. The current time and storage time can be displayed and printed at any time.
5. Scientific and advanced data management: Instrument data can be exported through U disk and can be viewed and managed on any PC by special software.
6. The instrument is easy to operate and the measurement process is controlled by microprocessor. As long as the appropriate measurement mode is selected, the measurement of data can be completed automatically under the control of microprocessor.
7. Integrated model, with standard capacitor and high voltage power supply, is convenient for field test and reduces field wiring.
8. The instrument has high accuracy and can meet the requirements of oil dielectric loss measurement. Therefore, only standard oil cup and special testing line are needed to realize oil dielectric loss measurement.
9. It has the function of low voltage shielding of reverse wiring. Under the condition of 220 kV CVT bus grounding, it can measure the dielectric loss of 110 kV reverse wiring without disconnection.
10. Be able to do AC withstand voltage test. It is convenient for PT and CT to do AC voltage withstanding test twice and 400V low voltage system to do voltage withstanding test.
11. It can identify the frequency of external high-voltage power supply from 40Hz to 70Hz, and allow large capacity and high voltage dielectric loss test with power frequency power supply or series resonant power supply.
12. It has the function of CVT test and can realize the self-excitation test of CVT. It can set four protection restrictions of high voltage/current and low voltage/current to ensure the safety of person and equipment.
13. When testing CVT, not only the capacitance and dielectric loss values of C1 and C2 can be automatically tested, but also the total capacitance and dielectric loss values of CVT equipment can be tested.
14. With a thermal printer, it can print out, with a calendar clock, to facilitate users to produce test reports, with U disk output.
15. With computer interface. A computer can control 32 instruments, which can be integrated into an integrated high-voltage test vehicle to realize measurement, data processing and report output.
16. Grounding protection function. When the instrument is not grounded or grounded badly, the instrument does not enter the normal procedure and does not output high voltage. Overcurrent protection function, the instrument will not be damaged when the sample is short-circuit or breakdown.High current protection function. When the operator of the instrument accidentally touches the electricity, the instrument will immediately cut off the high voltage to ensure the safety of the tester. The voltage can provide a maximum voltage of 10 kilovolts. The 50 Hz interference can be automatically filtered out, which is suitable for on-site testing of large electromagnetic interference such as substations. It is widely used in dielectric loss measurement of transformer, transformer, bushing, capacitor, lightning arrester and other equipment in power industry.
Technical Index
Accuracy : Cx: ±(Rd×1%+1pF)
tgδ: ±(Rd×1%+0.00040)
Anti-interference index:Variable frequency anti-interference,reach above accuracy under the condition of 200%
Capacitance range:Internal applied HV: 3pF~60000pF/12kV 60pF~1μF/0.5kV
External applied HV: 3pF~1.5μF/12kV 60pF~30μF/0.5kV
Resolution: Max. 0.001pF,4 valid digits
Tgδ range: No limit,resolution 0.001,Capacitance,inductance,resistance automatically
recognize
Current range:10μA~5A
Internal applied HV: voltage setting range:0.5~12kV
Max.output current:200mA
Buck-boost mode:voltage can be set arbitrarily
Test frequency : 40-70Hz Single Frequency Random Settings.E.g48.7Hz.
50±0.1Hz to 50±10HzAutomatic Double Frequency Converter Arbitrary Setting.
60±0.1Hz to 60±10HzAutomatic Double Frequency Converter Arbitrary Setting.
Frequency accuracy: ±0.01Hz
External applied HV:Max.test current at UST 5A,power frequency or variable frequency 40-70Hz
Max.test current at GST:10kV/5A,power frequency or variable frequency40-70Hz
CVT Low Voltage Output by Self-Excitation Method:Output voltage3~50V,
output current3~30A
Test time: about 40s,no consider of test mode
Power supply: 180V~270VAC,50Hz±1%,
PC port:standard RS232 port,U-disk socket (automatic U-disk storage data).
Printer:Miniature Thermal Printer
Ambient temperature:-10℃~50℃ Relative humidity: <90%
Dimension :430×330×350mm Weight:28kg